Data sheet

Mini contactors B6, BC6 with 3 pole

Mini contactors from ABB are used forremotely controlling motors and otherloads wherever space is at a premium.These devices feature hum free coils,shallow depth, and no limitationsregarding mounting orientation.

Description

– Rated for motor loads up to 4 kW @ 400 V and 3 hp @ 480 V– 3-pole with one built-in auxiliary contact

– Connection types: screw, soldering pin (PCB-mount) up to

12 A or flat pin (quick connect) up to 20 A – AC or DC control voltages

– Low power consumption, hum free coils– Acceptable use in any mounting position– Compact design with shallow depth

Order data

B6 3-pole with screw terminal BC6 3-pole with screw terminal

4 kW @ 400 V AC-3

AC operated

4 kW @ 400 V AC-3

DC operated

Rated con- Type Order code Packing Weight

trol circuit unit per pc

voltage

V AC pcs kg

Rated con- Type Order code Packing Weight

trol circuit unit per pc

voltage

V AC pcs kg

12 B6-30-01-14 GJL1211001R1014 10 0.175 6 BC6-30-01-06 GJL1213001R0016 10 0.175

12 B6-30-10-14 GJL1211001R1104 10 0.175 6 BC6-30-10-06 GJL1213001R0106 10 0.175

24 B6-30-01-01 GJL1211001R0011 10 0.175 12 BC6-30-01-07 GJL1213001R0017 10 0.175

24 B6-30-10-01 GJL1211001R0101 10 0.175 12 BC6-30-10-07 GJL1213001R0107 10 0.175

32 B6-30-01-18 GJL1211001R1018 10 0.175 20 BC6-30-10-09 GJL1213001R0109 10 0.175

32 B6-30-10-18 GJL1211001R1108 10 0.175

42 B6-30-01-02 GJL1211001R0012 10 0.175

24 BC6-30-01-01 GJL1213001R0011 10 0.175

24 BC6-30-10-01 GJL1213001R0101 10 0.175

42 B6-30-10-02 GJL1211001R0102 10 0.175 30 BC6-30-01-13 GJL1213001R1013 10 0.175

48 B6-30-01-03 GJL1211001R0013 10 0.175

48 B6-30-10-03 GJL1211001R0103 10 0.175

30 BC6-30-10-13 GJL1213001R1103 10 0.175

42 BC6-30-01-02 GJL1213001R0012 10 0.175

60 B6-30-01-22 GJL1211001R2012 10 0.175 42 BC6-30-10-02 GJL1213001R0102 10 0.175

60 B6-30-10-22 GJL1211001R2102 10 0.175 48 BC6-30-01-16 GJL1213001R1016 10 0.175

72 B6-30-01-23 GJL1211001R2013 10 0.175 48 BC6-30-10-16 GJL1213001R1106 10 0.175

110 … 127 B6-30-01-84 GJL1211001R8014 10 0.175 60 BC6-30-01-03 GJL1213001R0013 10 0.175

110 … 127 B6-30-10-84 GJL1211001R8104 10 0.175 60 BC6-30-10-03 GJL1213001R0103 10 0.175

200 B6-30-01-37 GJL1211001R3017 10 0.175

200 B6-30-10-37 GJL1211001R3107 10 0.175

72 BC6-30-01-21 GJL1213001R2101 10 0.175

75 BC6-30-01-22 GJL1213001R2012 10 0.175

220 … 240 B6-30-01-80 GJL1211001R8010 10 0.175 110 … 125 BC6-30-01-04 GJL1213001R0014 10 0.175

220 … 240 B6-30-10-80 GJL1211001R8100 10 0.175

380 … 415 B6-30-01-85 GJL1211001R8015 10 0.175

110 … 125 BC6-30-10-04 GJL1213001R0104 10 0.175

220 … 240 BC6-30-01-05 GJL1213001R0015 10 0.175

380 … 415 B6-30-10-85 GJL1211001R8105 10 0.175 220 … 240 BC6-30-10-05 GJL1213001R0105 10 0.175

250 BC6-30-10-34 GJL1213001R3104 10 0.175

B6 3-pole with soldering pin 1) BC6 3-pole (3 N.O.) with soldering pin 1)





4 kW @ 400 V AC-3 4 kW @ 400 V AC-3AC operated AC operated

Rated

control

circuit

voltage

Type Order code Packing

unit

Weight

per pc

Rated

control

circuit

voltage

Type Order code Packing

unit

Weight

per pc

V AC pcs kg V AC pcs kg

24 B6-30-10-P-01 GJL1211009R0101 10 0.170 12 BC6-30-10-P-07 GJL1213009R0107 10 0.170

24 B6-30-01-P-01 GJL1211009R0011 10 0.170 12 BC6-30-01-P-07 GJL1213009R0017 10 0.170

42 B6-30-10-P-02 GJL1211009R0102 10 0.170 24 BC6-30-10-P-01 GJL1213009R0101 10 0.170

42 B6-30-01-P-02 GJL1211009R0012 10 0.170

48 B6-30-10-P-03 GJL1211009R0103 10 0.170

24 BC6-30-01-P-01 GJL1213009R0011 10 0.170

48 BC6-30-10-P-16 GJL1213009R1106 10 0.170

48 B6-30-01-P-03 GJL1211009R0013 10 0.170 48 BC6-30-01-P-16 GJL1213009R1016 10 0.170

110 … 127 B6-30-10-P-84 GJL1211009R8104 10 0.170

110 … 127 B6-30-01-P-84 GJL1211009R8014 10 0.170

60 BC6-30-10-P-03 GJL1213009R0103 10 0.170

60 BC6-30-01-P-03 GJL1213009R0013 10 0.170

220 … 240 B6-30-10-P-80 GJL1211009R8100 10 0.170 110 … 125 BC6-30-10-P-04 GJL1213009R0104 10 0.170

220 … 240 B6-30-01-P-80 GJL1211009R8010 10 0.170 110 … 125 BC6-30-01-P-04 GJL1213009R0014 10 0.170

380 … 415 B6-30-10-P-85 GJL1211009R8105 10 0.170 220 … 240 BC6-30-10-P-05 GJL1213009R0105 10 0.170

380 … 415 B6-30-01-P-85 GJL1211009R8015 10 0.170 220 … 240 BC6-30-01-P-05 GJL1213009R0015 10 0.170

BC6 3-pole (2 N.O. + 1 N.C.) with soldering pin 1)

4 kW @ 400 V AC-3 AC operated

Rated

control

circuit

voltage

Type Order code Packing

unit

Weight

per pc

V AC pcs kg

24 BC6-21-10-P-01 GJL1213109R0101 10 0.170

8 BC6-21-10-P-16 GJL1213109R1106 10 0.170

60 BC6-21-10-P-03 GJL1213109R0103 10 0.170

110 … 125 BC6-21-10-P-04 GJL1213109R0104 10 0.170

220 … 240 BC6-21-10-P-05 GJL1213109R0105 10 0.170

B6 3-pole with flat pin 1) BC6 3-pole with flat pin 1)

4 kW @ 400 V AC-3 4 kW @ 400 V AC-3AC operated DC operated

Rated

control

circuit

voltage

Type Order code Packing

unit

Weight

per pc

Rated

control

circuit

voltage

Type Order code Packing

unit

Weight

per pc

V AC pcs kg V DC pcs kg

24 B6-30-10-F-01 GJL1211003R0101 10 0.170 12 BC6-30-10-F-07 GJL1213003R0107 10 0.170

24 B6-30-01-F-01 GJL1211003R0011 10 0.170 12 BC6-30-01-F-07 GJL1213003R0017 10 0.170

42 B6-30-10-F-02 GJL1211003R0102 10 0.170 24 BC6-30-10-F-01 GJL1213003R0101 10 0.170

42 B6-30-01-F-02 GJL1211003R0012 10 0.170 24 BC6-30-01-F-01 GJL1213003R0011 10 0.170

48 B6-30-10-F-03 GJL1211003R0103 10 0.170 48 BC6-30-10-F-16 GJL1213003R1106 10 0.170

48 B6-30-01-F-03 GJL1211003R0013 10 0.170 48 BC6-30-01-F-16 GJL1213003R1016 10 0.170

110 … 127 B6-30-10-F-84 GJL1211003R8104 10 0.170 60 BC6-30-01-F-03 GJL1213003R0013 10 0.170

110 … 127 B6-30-01-F-84 GJL1211003R8014 10 0.170 110 … 125 BC6-30-10-F-04 GJL1213003R0104 10 0.170

220 … 240 B6-30-10-F-80 GJL1211003R8100 10 0.170 110 … 125 BC6-30-01-F-04 GJL1213003R0014 10 0.170

220 … 240 B6-30-01-F-80 GJL1211003R8010 10 0.170

380 … 415 B6-30-10-F-85 GJL1211003R8105 10 0.170

380 … 415 B6-30-01-F-85 GJL1211003R8015 10 0.170

220 … 240 BC6-30-10-F-05 GJL1213003R0105 10 0.170

220 … 240 BC6-30-01-F-05 GJL1213003R0015 10 0.170

1) Soldering pin connection acc. to DIN 40801: 0.8 x 1 mm / 0.8 x 2.54 mm

Flat pin connection acc. to DIN 46248: 1 x 6.3 mm / 1 x 2.8 mm

2 – 2CDC102053D0201

Functional description













1

1 Wall mounting (two diagonally arranged M4 screws)

2 Main terminals – 1L1, 3L2, 5L3

3 Auxiliary terminal – 13 NO or 21 NC 2

3 4 Coil terminal A1

4

5 Front extra auxiliary contact mounts

6 Side extra auxiliary contact mount

5

7 Coil terminal A2

8 Auxiliary terminal – 14 NO or 22 NC

6

2 7

120 Mounting on DIN-rail (rear side) 8

9

10

Application

B6 contactors are capable of switching power circuits up to 690 V AC. They are mainly used for controlling single and three-phase motors (AC-3) and non-inductive or slightly inductive loads (AC-1). Standard versions include either 3 normally-openmain poles with 1 auxiliary contact or 4 main poles in various configurations. Additional auxiliary contacts for front or sidemounting are available as accessories. Mini contactors can be mounted in any position (including upside down) withoutderating.

Operation mode

A1 1L1 3L2 5L3

13 A1 1L1 3L2

NO

5L3

21

NC

A2 2T1 4T2 6T3

NO

14

A2

2T1

4T2

6T3

NC

22

B6-30-10 / BC6-30-10 B6-30-01 / BC6-30-01

Terminal marking

1 3 5 13 A1 1 3 5 21 A1

2 4 6 14 A2 2 4 6 22 A2

B6-30-10 … /

BC6-30-10 …

B6-30-01 … /

BC6-30-01 …

2CDC102053D0201 – 3

Dimensions




in mm and inches

52.5 2.07″ 46.7 1.84″

47.5 1.87″ 43.7 1.72″

4.5 0.18″

B(C)6 – Connection: Screws

47.7 1.88″ 4.3 0.17″

47.5 1.87″ 44.7 1.76″

B(C)6 – Connection: Soldering pins

52.5 2.07″

46.7 1.84″

47.5 1.87″ 43.7 1.72″

4.5 0.18″

B(C)6 – Connection: Flat pin (Faston)

4 – 2CDC102053D0201

Technical data



Main pole – utilization characteristics according to IEC

Standards IEC/EN 60947-1

IEC/EN 60947-4-1

IEC/EN 60947-5-1

Rated operational voltage main circuit 690 V AC Rated frequency main circuit 50 Hz, 60 Hz, DC Conventional free-air thermal current main circuit 20 A Rated operational current AC-1 (220/240 V) 40 °C 20 A (380/440 V) 40 °C 20 A

(500 V) 40 °C 12 A

(690 V) 40 °C 6 A

(220/240 V) 55 °C 16 A

(380/440 V) 55 °C 16 A

(500 V) 55 °C 12 A

(690 V) 55 °C 6 A Rated operational current AC-3 (220 V) 55 °C 8.9 A (230 V) 55 °C 8.5 A (240 V) 55 °C 8.1 A (380 V) 55 °C 8.9 A (400 V) 55 °C 8.5 A (440 V) 55 °C 7.4 A (500 V) 55 °C 6.8 A (690 V) 55 °C 3.8 A

Rated operational power AC-3 (220/230/240 V) 2.2 kW (380/400 V) 4.0 kW

(440 V) 4.0 kW

(500 V) 4.0 kW

(690 V) 3.0 kW Rated making capacity AC-3 acc. to IEC 60947-4-1 10 x Ie AC3Rated breaking capacity AC-3 acc. to IEC 60947-4-1 8 x Ie AC3Co-ordination with short-circuit protective devices – type 1 690 V AC – gG Type Fuses 25 ACo-ordination with short-circuit protective devices – type 2 690 V AC – gG Type Fuses 20 ARated short-time withstand current at 40 °C ambient temp, in free air, from 64 kA

a cold state 10 s

Maximum electrical switching frequency AC-1 300 cycles per hour

AC-3 300 cycles per hour

Main pole – utilization characteristics according to UL

Standards UL 60947-1

UL 60947-4-1

General use rating UL/CSA 300 V AC 12 A

600 V AC –

Maximum motor rating UL/CSA full load current three phase (200 V) 4.8 A

full load current three phase (208 V) 4.6 A

full load current three phase (220/240 V) 6.8 A

full load current three phase (440/480 V) 4.8 A

full load current three phase (550/600 V) 1.7 A Horsepower rating UL/CSA 208 V AC three phase 1 hp 220 … 240 V AC three phase 2 hp 440 … 480 V AC three phase 3 hp 550 … 600 V AC three phase 1 hp

Maximum electrical switching frequency AC-1 300 cycles per hour

AC-3 300 cycles per hour

2CDC102053D0201 – 5