Data sheet
Mini contactors B6, BC6 with 3 pole
Mini contactors from ABB are used forremotely controlling motors and otherloads wherever space is at a premium.These devices feature hum free coils,shallow depth, and no limitationsregarding mounting orientation.
Description
– Rated for motor loads up to 4 kW @ 400 V and 3 hp @ 480 V– 3-pole with one built-in auxiliary contact
– Connection types: screw, soldering pin (PCB-mount) up to
12 A or flat pin (quick connect) up to 20 A – AC or DC control voltages
– Low power consumption, hum free coils– Acceptable use in any mounting position– Compact design with shallow depth
Order data
B6 3-pole with screw terminal BC6 3-pole with screw terminal
4 kW @ 400 V AC-3 AC operated |
4 kW @ 400 V AC-3 DC operated |
||
Rated con- Type Order code Packing Weight trol circuit unit per pc voltage V AC pcs kg |
Rated con- Type Order code Packing Weight trol circuit unit per pc voltage V AC pcs kg |
12 B6-30-01-14 GJL1211001R1014 10 0.175 6 BC6-30-01-06 GJL1213001R0016 10 0.175
12 B6-30-10-14 GJL1211001R1104 10 0.175 6 BC6-30-10-06 GJL1213001R0106 10 0.175
24 B6-30-01-01 GJL1211001R0011 10 0.175 12 BC6-30-01-07 GJL1213001R0017 10 0.175
24 B6-30-10-01 GJL1211001R0101 10 0.175 12 BC6-30-10-07 GJL1213001R0107 10 0.175
32 B6-30-01-18 GJL1211001R1018 10 0.175 20 BC6-30-10-09 GJL1213001R0109 10 0.175
32 B6-30-10-18 GJL1211001R1108 10 0.175 42 B6-30-01-02 GJL1211001R0012 10 0.175 |
24 BC6-30-01-01 GJL1213001R0011 10 0.175 24 BC6-30-10-01 GJL1213001R0101 10 0.175 |
42 B6-30-10-02 GJL1211001R0102 10 0.175 30 BC6-30-01-13 GJL1213001R1013 10 0.175
48 B6-30-01-03 GJL1211001R0013 10 0.175 48 B6-30-10-03 GJL1211001R0103 10 0.175 |
30 BC6-30-10-13 GJL1213001R1103 10 0.175 42 BC6-30-01-02 GJL1213001R0012 10 0.175 |
60 B6-30-01-22 GJL1211001R2012 10 0.175 42 BC6-30-10-02 GJL1213001R0102 10 0.175
60 B6-30-10-22 GJL1211001R2102 10 0.175 48 BC6-30-01-16 GJL1213001R1016 10 0.175
72 B6-30-01-23 GJL1211001R2013 10 0.175 48 BC6-30-10-16 GJL1213001R1106 10 0.175
110 … 127 B6-30-01-84 GJL1211001R8014 10 0.175 60 BC6-30-01-03 GJL1213001R0013 10 0.175
110 … 127 B6-30-10-84 GJL1211001R8104 10 0.175 60 BC6-30-10-03 GJL1213001R0103 10 0.175
200 B6-30-01-37 GJL1211001R3017 10 0.175 200 B6-30-10-37 GJL1211001R3107 10 0.175 |
72 BC6-30-01-21 GJL1213001R2101 10 0.175 75 BC6-30-01-22 GJL1213001R2012 10 0.175 |
220 … 240 B6-30-01-80 GJL1211001R8010 10 0.175 110 … 125 BC6-30-01-04 GJL1213001R0014 10 0.175
220 … 240 B6-30-10-80 GJL1211001R8100 10 0.175 380 … 415 B6-30-01-85 GJL1211001R8015 10 0.175 |
110 … 125 BC6-30-10-04 GJL1213001R0104 10 0.175 220 … 240 BC6-30-01-05 GJL1213001R0015 10 0.175 |
380 … 415 B6-30-10-85 GJL1211001R8105 10 0.175 220 … 240 BC6-30-10-05 GJL1213001R0105 10 0.175
250 BC6-30-10-34 GJL1213001R3104 10 0.175
B6 3-pole with soldering pin 1) BC6 3-pole (3 N.O.) with soldering pin 1)
4 kW @ 400 V AC-3 4 kW @ 400 V AC-3AC operated AC operated
Rated control circuit voltage |
Type Order code Packing unit |
Weight per pc |
Rated control circuit voltage |
Type Order code Packing unit |
Weight per pc |
V AC pcs kg V AC pcs kg
24 B6-30-10-P-01 GJL1211009R0101 10 0.170 12 BC6-30-10-P-07 GJL1213009R0107 10 0.170
24 B6-30-01-P-01 GJL1211009R0011 10 0.170 12 BC6-30-01-P-07 GJL1213009R0017 10 0.170
42 B6-30-10-P-02 GJL1211009R0102 10 0.170 24 BC6-30-10-P-01 GJL1213009R0101 10 0.170
42 B6-30-01-P-02 GJL1211009R0012 10 0.170 48 B6-30-10-P-03 GJL1211009R0103 10 0.170 |
24 BC6-30-01-P-01 GJL1213009R0011 10 0.170 48 BC6-30-10-P-16 GJL1213009R1106 10 0.170 |
48 B6-30-01-P-03 GJL1211009R0013 10 0.170 48 BC6-30-01-P-16 GJL1213009R1016 10 0.170
110 … 127 B6-30-10-P-84 GJL1211009R8104 10 0.170 110 … 127 B6-30-01-P-84 GJL1211009R8014 10 0.170 |
60 BC6-30-10-P-03 GJL1213009R0103 10 0.170 60 BC6-30-01-P-03 GJL1213009R0013 10 0.170 |
220 … 240 B6-30-10-P-80 GJL1211009R8100 10 0.170 110 … 125 BC6-30-10-P-04 GJL1213009R0104 10 0.170
220 … 240 B6-30-01-P-80 GJL1211009R8010 10 0.170 110 … 125 BC6-30-01-P-04 GJL1213009R0014 10 0.170
380 … 415 B6-30-10-P-85 GJL1211009R8105 10 0.170 220 … 240 BC6-30-10-P-05 GJL1213009R0105 10 0.170
380 … 415 B6-30-01-P-85 GJL1211009R8015 10 0.170 220 … 240 BC6-30-01-P-05 GJL1213009R0015 10 0.170
BC6 3-pole (2 N.O. + 1 N.C.) with soldering pin 1)
4 kW @ 400 V AC-3 AC operated
Rated control circuit voltage |
Type Order code Packing unit |
Weight per pc |
V AC pcs kg
24 BC6-21-10-P-01 GJL1213109R0101 10 0.170
8 BC6-21-10-P-16 GJL1213109R1106 10 0.170
60 BC6-21-10-P-03 GJL1213109R0103 10 0.170
110 … 125 BC6-21-10-P-04 GJL1213109R0104 10 0.170
220 … 240 BC6-21-10-P-05 GJL1213109R0105 10 0.170
B6 3-pole with flat pin 1) BC6 3-pole with flat pin 1)
4 kW @ 400 V AC-3 4 kW @ 400 V AC-3AC operated DC operated
Rated control circuit voltage |
Type Order code Packing unit |
Weight per pc |
Rated control circuit voltage |
Type Order code Packing unit |
Weight per pc |
V AC pcs kg V DC pcs kg
24 B6-30-10-F-01 GJL1211003R0101 10 0.170 12 BC6-30-10-F-07 GJL1213003R0107 10 0.170
24 B6-30-01-F-01 GJL1211003R0011 10 0.170 12 BC6-30-01-F-07 GJL1213003R0017 10 0.170
42 B6-30-10-F-02 GJL1211003R0102 10 0.170 24 BC6-30-10-F-01 GJL1213003R0101 10 0.170
42 B6-30-01-F-02 GJL1211003R0012 10 0.170 24 BC6-30-01-F-01 GJL1213003R0011 10 0.170
48 B6-30-10-F-03 GJL1211003R0103 10 0.170 48 BC6-30-10-F-16 GJL1213003R1106 10 0.170
48 B6-30-01-F-03 GJL1211003R0013 10 0.170 48 BC6-30-01-F-16 GJL1213003R1016 10 0.170
110 … 127 B6-30-10-F-84 GJL1211003R8104 10 0.170 60 BC6-30-01-F-03 GJL1213003R0013 10 0.170
110 … 127 B6-30-01-F-84 GJL1211003R8014 10 0.170 110 … 125 BC6-30-10-F-04 GJL1213003R0104 10 0.170
220 … 240 B6-30-10-F-80 GJL1211003R8100 10 0.170 110 … 125 BC6-30-01-F-04 GJL1213003R0014 10 0.170
220 … 240 B6-30-01-F-80 GJL1211003R8010 10 0.170 380 … 415 B6-30-10-F-85 GJL1211003R8105 10 0.170 380 … 415 B6-30-01-F-85 GJL1211003R8015 10 0.170 |
220 … 240 BC6-30-10-F-05 GJL1213003R0105 10 0.170 220 … 240 BC6-30-01-F-05 GJL1213003R0015 10 0.170 |
1) Soldering pin connection acc. to DIN 40801: 0.8 x 1 mm / 0.8 x 2.54 mm
Flat pin connection acc. to DIN 46248: 1 x 6.3 mm / 1 x 2.8 mm
2 – 2CDC102053D0201
Functional description
1
1 Wall mounting (two diagonally arranged M4 screws)
2 Main terminals – 1L1, 3L2, 5L3
3 Auxiliary terminal – 13 NO or 21 NC 2
3 4 Coil terminal A1
4
5 Front extra auxiliary contact mounts
6 Side extra auxiliary contact mount
5
7 Coil terminal A2
8 Auxiliary terminal – 14 NO or 22 NC
6
2 7
120 Mounting on DIN-rail (rear side) 8
9
10
Application
B6 contactors are capable of switching power circuits up to 690 V AC. They are mainly used for controlling single and three-phase motors (AC-3) and non-inductive or slightly inductive loads (AC-1). Standard versions include either 3 normally-openmain poles with 1 auxiliary contact or 4 main poles in various configurations. Additional auxiliary contacts for front or sidemounting are available as accessories. Mini contactors can be mounted in any position (including upside down) withoutderating.
Operation mode
A1 1L1 3L2 5L3 |
13 A1 1L1 3L2 NO |
5L3 |
21 NC |
||||||||||||||||
A2 2T1 4T2 6T3 |
NO 14 |
A2 |
2T1 |
4T2 |
6T3 |
NC 22 |
B6-30-10 / BC6-30-10 B6-30-01 / BC6-30-01
Terminal marking
1 3 5 13 A1 1 3 5 21 A1
2 4 6 14 A2 2 4 6 22 A2
B6-30-10 … / BC6-30-10 … |
B6-30-01 … / BC6-30-01 … |
2CDC102053D0201 – 3
Dimensions
in mm and inches
52.5 2.07″ 46.7 1.84″
47.5 1.87″ 43.7 1.72″
4.5 0.18″
B(C)6 – Connection: Screws
47.7 1.88″ 4.3 0.17″
47.5 1.87″ 44.7 1.76″
B(C)6 – Connection: Soldering pins
52.5 2.07″
46.7 1.84″
47.5 1.87″ 43.7 1.72″
4.5 0.18″
B(C)6 – Connection: Flat pin (Faston)
4 – 2CDC102053D0201
Technical data
Main pole – utilization characteristics according to IEC
Standards IEC/EN 60947-1
IEC/EN 60947-4-1
IEC/EN 60947-5-1
Rated operational voltage main circuit 690 V AC Rated frequency main circuit 50 Hz, 60 Hz, DC Conventional free-air thermal current main circuit 20 A Rated operational current AC-1 (220/240 V) 40 °C 20 A (380/440 V) 40 °C 20 A
(500 V) 40 °C 12 A
(690 V) 40 °C 6 A
(220/240 V) 55 °C 16 A
(380/440 V) 55 °C 16 A
(500 V) 55 °C 12 A
(690 V) 55 °C 6 A Rated operational current AC-3 (220 V) 55 °C 8.9 A (230 V) 55 °C 8.5 A (240 V) 55 °C 8.1 A (380 V) 55 °C 8.9 A (400 V) 55 °C 8.5 A (440 V) 55 °C 7.4 A (500 V) 55 °C 6.8 A (690 V) 55 °C 3.8 A
Rated operational power AC-3 (220/230/240 V) 2.2 kW (380/400 V) 4.0 kW
(440 V) 4.0 kW
(500 V) 4.0 kW
(690 V) 3.0 kW Rated making capacity AC-3 acc. to IEC 60947-4-1 10 x Ie AC3Rated breaking capacity AC-3 acc. to IEC 60947-4-1 8 x Ie AC3Co-ordination with short-circuit protective devices – type 1 690 V AC – gG Type Fuses 25 ACo-ordination with short-circuit protective devices – type 2 690 V AC – gG Type Fuses 20 ARated short-time withstand current at 40 °C ambient temp, in free air, from 64 kA
a cold state 10 s
Maximum electrical switching frequency AC-1 300 cycles per hour
AC-3 300 cycles per hour
Main pole – utilization characteristics according to UL
Standards UL 60947-1
UL 60947-4-1
General use rating UL/CSA 300 V AC 12 A
600 V AC –
Maximum motor rating UL/CSA full load current three phase (200 V) 4.8 A
full load current three phase (208 V) 4.6 A
full load current three phase (220/240 V) 6.8 A
full load current three phase (440/480 V) 4.8 A
full load current three phase (550/600 V) 1.7 A Horsepower rating UL/CSA 208 V AC three phase 1 hp 220 … 240 V AC three phase 2 hp 440 … 480 V AC three phase 3 hp 550 … 600 V AC three phase 1 hp
Maximum electrical switching frequency AC-1 300 cycles per hour
AC-3 300 cycles per hour
2CDC102053D0201 – 5
2CDC102053D0201